If you have a diesel generator set , you should need to learn how to use it correctly. Maybe the article below can tell you something.
First, check before starting the generator :
1, check the oil and water are within the normal range;
2, check the battery and the battery cable is normal;
3, check the fuel valve whether is open, whether the fuel can supply the normal generators;
4, check the control box lights are in working order, where there is a fault indication, please repair timely;
5, in order to start the battery and extend the life of the start motor, a start time of the control unit is appropriate in 5-10 seconds, if a start is unsuccessful, you can pause the appropriate time to start the program a second time;
6, power generation equipment is ready to load, when the generator directly with the load, before the start of the air switch to be breaking.
Second, the diesel engine Note:
1 in operation, should check the water temperature, oil pressure, frequency, current, etc. whether they are in normal, such as generator power distribution failure or severe failure of crew to stop immediately;
2, K38 Cummins unit current does not allow more than 900A, German Man does not allow more than 600A, otherwise it will lead to unit failure, reduce unit service life;
3, is strictly prohibited to disassemble the unit operation, the replacement unit on the parts;
4, must meet the national standard fuel, otherwise it will cause generator or a fuel injector pump failure;
5, the unit can not afford to run more than 50% of sudden load, otherwise, the stall will cause a larger unit, recommended for large electrical equipment, taking blood pressure, frequency and other methods to control the start, to slow the startup of the unit generated greater impact;
6, the spare unit or the unit does not run a long time, it is recommended once a month to at least the unit operating temperature, let the unit at least once a year with a full load to run about 4 hours, which can be burned within the engine and exhaust system product carbon.
Third, the above operators should apply to chapter operations, timely maintenance, to keep the unit normal operation, so as to avoid unnecessary losses caused by the company, and make generators run record.